Short Description:

Electrical insulation wrinkle paper has good mechanical strength, high voltage resistance, smooth surface and toughness. The cutting of insulating paperboard is convenient. After bending, it still maintains a certain strength, especially in oil immersion. This feature is very good to protect the transformer lead wire from being squeezed and broken, which not only meets the requirements of insulation, but also meets the requirements of mechanical properties


Product Detail

The Detail Information of Crepe Paper 

Description     Crepe paper 0.46mm  
M.F.Date 2013.7 Size

40*130mm

  Standard

MD

CD

TD

Thickness 0.4-0.5mm

0.476

Basis weight g/m²  

127.2

Density g/cm² 0.2-0.35

0.27

Tension strength kg/15mm MD 4.0

6.1

Elongation % 100-140

127.9

Dielectric breakdown strength KV Ave. ≥1.10

AVC.1.29

Min.1.21

 
  Min ≥0.80

 

 

 
Moisture content % ≤0.8

5.1

Ash content % ≤0.7

0.329

Protuberances numbers/inch 20-40

31